Skip to main content
Siemens 6ES7144-6JF00-0BB0

Siemens 6ES7144-6JF00-0BB0 Temperature RTD TC Module, IRT 25

MPN 6ES7144-6JF00-0BB0
Active

Siemens SIMATIC ET200SP, 6ES7144-6JF00-0BB0, temperature input module, 2x M12 ports, PROFINET with IRT 250 µs.

$267.97 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6ES7144-6JF00-0BB0 specifications
ParameterValue
IP ratingIP65
Temp operating max5 °C
Temp operating min1 °C
Depth48 mm
Width45 mm
Height200 mm
Measurement principleIntegrating
Temperature error of internal compensation±1,5 °C

Product details

Siemens 6ES7144-6JF00-0BB0 is a PROFINET IO module for direct connection of resistance thermometers (Pt100, Pt1000, Ni100 etc.) and thermocouples (types B, C, E, J, K, L, N, R, S, T, U). Two M12, 4-pin, D-coded ports bring sensor wiring directly into the module, eliminating separate junction boxes. IRT is supported with a cycle time from 250 µs to 4 ms in 125 µs frames, placing it on high-speed deterministic networks alongside ARP, MRP, MSI, and LLDP.

Dimensions are 45 mm wide, 200 mm high, and 48 mm deep. Status diagnostics via RUN/ERROR/IO/MS/NS LEDs (red, green, yellow).

Sensor compatibility

Supports Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000 in standard and climate ranges, plus Pt1000 and Ni1000. All RTD inputs are 16-bit including sign. Thirteen thermocouple types are covered, all at 16-bit resolution with sign. This module covers the full temperature sensing spectrum for furnace, HVAC, and process applications.

The module occupies 16 input bytes plus 1 byte for QI information per the PROFINET IO data model. This is a fixed I/O footprint typical for temperature slices — plan your IO mapping accordingly. No expansion bus is needed beyond the two M12 ports; each port handles a single sensor.

MPN
6ES7144-6JF00-0BB0