Skip to main content
Siemens 3RV1041-4FA10-ZX95

Siemens 3RV1041-4FA10-ZX95 SIRIUS Motor Protection Circuit B

MPN 3RV1041-4FA10-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV1041-4FA10-ZX95, 40 A rated continuous current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, 3-pole, screw terminals.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1041-4FA10-ZX95 specifications
ParameterValue
Depth174 mm
Width70 mm
Height165 mm
Trip classCLASS 10

Product details

It combines a circuit breaker and overload relay in one unit, saving panel space and wiring time. The 40 A continuous rating and CLASS 10 trip characteristic mean it handles inrush on standard induction motors up to about 18.5 kW at 400 V and trips fast enough to protect the motor during a stall or jam — not so fast that nuisance trips plague you on startup.

Breaking capacity and fault handling

This breaker is rated to interrupt 100 kA at 240 V, 50 kA at 400 V, 12 kA at 500 V, and 6 kA at 690 V. Those numbers tell you it can handle a dead short on a high-capacity transformer without welding its contacts shut — a key selectivity consideration for the site electrical engineer. The 690 V rated value means it's fine on 480/600 V systems common in North America, not just 400 V European grids.

Width is 70 mm, depth 174 mm, height 165 mm — that's a standard three-pole MCCB footprint, so it'll fit existing panel cutouts. Terminal wiring accepts solid 2x (2.5 to 16 mm²) or stranded 2x (10 to 50 mm²) and 1x (10 to 70 mm²), with AWG equivalents listed for the main contacts. The screw-type box terminals are familiar to any panel wireman; no special crimp tools needed. Mounting position is any, which helps when you're shoehorning this into a tight gland plate layout.

Environmental toughness

That's enough for unheated warehouses or hot Texas pump houses. Shock rated at 25g for 11 ms — it'll stay latched through a forklift bump or a compressor start jolt.

Power dissipation and auxiliary options

Dissipates 23 W in hot operating state (7.7 W per pole). The product extension for auxiliary switches is supported, so you can add a remote status contact for the PLC or a shunt trip for emergency-stop circuits.

MPN
3RV1041-4FA10-ZX95