Siemens 3RV1041-4FA10-ZX95 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV1041-4FA10-ZX95 SIRIUS Motor Protection Circuit B

MPN3RV1041-4FA10-ZX95

Siemens SIRIUS motor protection circuit breaker, 3RV1041-4FA10-ZX95, 40 A rated continuous current, CLASS 10 trip class, 50 kA breaking capacity at 400 V AC, 3-pole, screw terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RV1041-4FA10-ZX95 — Identification
ParameterValue
SeriesSIRIUS
Product designationcircuit breaker
3RV1041-4FA10-ZX95 — Electrical
ParameterValue
Rated voltage690 V
Rated voltage, AC-3 (max.)690 V
Rated impulse withstand voltage (Uimp)6 000 V
Number of poles3
Power loss (AC, hot)23 W
Power loss, per pole (AC, hot)7.7 W
3RV1041-4FA10-ZX95 — Protection & Tripping
ParameterValue
Overload release setting range28 ... 40 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)50 kA
Breaking capacity at 500 V (AC)12 kA
Breaking capacity at 690 V (AC)6 kA
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV1041-4FA10-ZX95 — Endurance & Switching
ParameterValue
Auxiliary CO (changeover) contacts0
3RV1041-4FA10-ZX95 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals with box terminals
Main-circuit connector arrangementfront side
Conductor cross-section, finely stranded with ferrule2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
Conductor range, AWG (main contacts)2x (10 ... 1), 1x (10 ... 2)
3RV1041-4FA10-ZX95 — Mechanical
ParameterValue
Height165 mm
Width70 mm
Depth174 mm
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Mounting positionany
3RV1041-4FA10-ZX95 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Max. installation altitude2 000 m
3RV1041-4FA10-ZX95 — Specifications
ParameterValue
Design Of The Productfor motor protection

Product details

It combines a circuit breaker and overload relay in one unit, saving panel space and wiring time. The 40 A continuous rating and CLASS 10 trip characteristic mean it handles inrush on standard induction motors up to about 18.5 kW at 400 V and trips fast enough to protect the motor during a stall or jam — not so fast that nuisance trips plague you on startup.

Breaking capacity and fault handling

This breaker is rated to interrupt 100 kA at 240 V, 50 kA at 400 V, 12 kA at 500 V, and 6 kA at 690 V. Those numbers tell you it can handle a dead short on a high-capacity transformer without welding its contacts shut — a key selectivity consideration for the site electrical engineer. The 690 V rated value means it's fine on 480/600 V systems common in North America, not just 400 V European grids.

Width is 70 mm, depth 174 mm, height 165 mm — that's a standard three-pole MCCB footprint, so it'll fit existing panel cutouts. Terminal wiring accepts solid 2x (2.5 to 16 mm²) or stranded 2x (10 to 50 mm²) and 1x (10 to 70 mm²), with AWG equivalents listed for the main contacts. The screw-type box terminals are familiar to any panel wireman; no special crimp tools needed. Mounting position is any, which helps when you're shoehorning this into a tight gland plate layout.

Environmental toughness

That's enough for unheated warehouses or hot Texas pump houses. Shock rated at 25g for 11 ms — it'll stay latched through a forklift bump or a compressor start jolt.

Power dissipation and auxiliary options

Dissipates 23 W in hot operating state (7.7 W per pole). The product extension for auxiliary switches is supported, so you can add a remote status contact for the PLC or a shunt trip for emergency-stop circuits.

Frequently asked questions

Will the 3RV1041-4FA10-ZX95 drop into a panel wired for a 3RV6021-4DA10?

Both are SIRIUS motor protection breakers on the same DIN-rail footprint, so the mounting and terminal spacing should match. However, verify the terminal wire range and auxiliary contact arrangement against your specific wiring — the 3RV1041-4FA10-ZX95 uses screw-type box terminals with the listed solid and stranded ranges, which may differ from the 3RV6021-4DA10.