Skip to main content
Siemens 4EU3921-6BA00-0A

4EU3921-6BA00-0A Commutating Choke, 710A AC, 500V, 50Hz

MPN 4EU3921-6BA00-0A

Siemens 4EU3921-6BA00-0A, commutating choke for converter, 3-phase, 710A AC / 870A DC, 500V, 50Hz, IP00, flat-type terminals, UL/CSA recognized.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

4EU3921-6BA00-0A specifications
ParameterValue
IP ratingIP00
Depth0.229 m
Width0.41 m
Height0.385 m

Product details

What this choke does in the drive cell

The Siemens 4EU3921-6BA00-0A is a 3-phase commutating choke (line reactor) for converter front-ends, rated 710 A AC continuous (639 A operational) at 500 V, 50 Hz, with a DC rated current of 870 A and a peak current capability of 888 A. The IP00 open-frame construction means it mounts inside a panel or enclosure that provides its own protection — no exposed installation in a washdown or dusty area.

Thermal class H and power loss budget

Thermal class H (180 °C winding hot-spot) per IEC 60085 lets this choke run hot — useful when it shares a cabinet with drives that raise ambient well above 40 °C. Total power loss splits 378 W in the coil and 210 W in the iron core at rated load, so the panel ventilation needs to clear roughly 590 W of heat from this one component. The 40 °C ambient rating is the reference point; above that, derate the continuous current.

Termination and physical fit

Main circuit connection uses flat-type terminals — expect bus-bar or large-lug cabling, not ring-tongue on a terminal block. Dimensions are 0.41 m wide × 0.385 m high × 0.229 m deep, so it needs a clear footprint on the panel floor or a dedicated mounting plate. IP00 means no touch protection; the enclosure must provide the guarding.

The choke is UL/CSA recognized and designed to EN 61558-2-20, covering safety of transformers, reactors, and power supply units. That recognition matters for panel builders who need a UL 508A listed component in the BOM.

MPN