Skip to main content
Siemens 4EU3921-6BA00-0A — Line/Load Reactors

4EU3921-6BA00-0A Commutating Choke, 710A AC, 500V, 50Hz

MPN4EU3921-6BA00-0A

Siemens 4EU3921-6BA00-0A, commutating choke for converter, 3-phase, 710A AC / 870A DC, 500V, 50Hz, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-6BA00-0A — Inductance & Impedance
ParameterValue
Rated inductance3.9E-5H
Relative inductive voltage drop4%
4EU3921-6BA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-6BA00-0A — Electrical
ParameterValue
Rated operating voltage500V
Rated current (AC)639A
Number of phases3
Current (AC), max.710A
Rated current (DC)870A
Voltage typeAC
Rated operating frequency50Hz
Peak current888A
4EU3921-6BA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)378W
Power loss, iron core (W)210W
Rated ambient temperature40°C
4EU3921-6BA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-6BA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

What this choke does in the drive cell

The Siemens 4EU3921-6BA00-0A is a 3-phase commutating choke (line reactor) for converter front-ends, rated 710 A AC continuous (639 A operational) at 500 V, 50 Hz, with a DC rated current of 870 A and a peak current capability of 888 A. The IP00 open-frame construction means it mounts inside a panel or enclosure that provides its own protection — no exposed installation in a washdown or dusty area.

Thermal class H and power loss budget

Thermal class H (180 °C winding hot-spot) per IEC 60085 lets this choke run hot — useful when it shares a cabinet with drives that raise ambient well above 40 °C. Total power loss splits 378 W in the coil and 210 W in the iron core at rated load, so the panel ventilation needs to clear roughly 590 W of heat from this one component. The 40 °C ambient rating is the reference point; above that, derate the continuous current.

Termination and physical fit

Main circuit connection uses flat-type terminals — expect bus-bar or large-lug cabling, not ring-tongue on a terminal block. Dimensions are 0.41 m wide × 0.385 m high × 0.229 m deep, so it needs a clear footprint on the panel floor or a dedicated mounting plate. IP00 means no touch protection; the enclosure must provide the guarding.

The choke is UL/CSA recognized and designed to EN 61558-2-20, covering safety of transformers, reactors, and power supply units. That recognition matters for panel builders who need a UL 508A listed component in the BOM.

Frequently asked questions

Where can I buy the 4EU3921-6BA00-0A?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key electrical ratings of the 4EU3921-6BA00-0A?

Rated 710 A AC continuous (639 A operational) at 500 V, 50 Hz, with a DC rated current of 870 A and a peak current of 888 A. Inductance is 0.0392 mH with a 4 % relative inductive voltage drop.

What compliance documentation does this choke carry?

It is UL/CSA recognized and designed to EN 61558-2-20.

What are the physical dimensions of the 4EU3921-6BA00-0A?

Width 0.41 m, height 0.385 m, depth 0.229 m. IP00 open-frame construction.

MPN
4EU3921-6BA00-0A