Skip to main content
Siemens 6EP1336-3BA00

Siemens 6EP1336-3BA00 SITOP Modular 20 A 24 V Power Supply

MPN 6EP1336-3BA00
NRND

Siemens SITOP modular power supply, 6EP1336-3BA00, 24 V DC output, 20 A rated current, dual AC input 120/230 V, DIN rail mount, IP20.

$254.00 – $512.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6EP1336-3BA00 specifications
ParameterValue
Voltage24 V
Power480 W
Frequency47 ... 63 Hz
Phases1-phase
IP ratingIP20
MountingSnaps onto DIN rail EN 60715 35x7.5/15
Depth125 mm
Width160 mm
Height125 mm
Efficiency89%

Product details

Panel fit and input flexibility

The 6EP1336-3BA00: Snaps onto DIN rail EN 60715 35x7.5/15 — the 50 mm top and bottom clearance keeps airflow natural for convection cooling. Dual AC input covers 85–132 V (120 V nominal) and 176–264 V (230 V nominal) at 50/60 Hz, so one part number handles both common line voltages without a jumper change. Input wiring uses one screw terminal each for L, N, PE accepting 0.2–4 mm²; output side has two terminals each for + and – accepting 0.5–4 mm².

Output rating and thermal derating

Rated 20 A continuous at 24 V DC from 0 to +60 °C with natural convection — above 60 °C derate 3.5% per K up to 70 °C ambient. Safety extra-low output voltage (SELV) per EN 60950-1 and EN 50178, so the 24 V rail is touch-safe for control circuits and field devices. MTBF 786,164 hours at 40 °C — the reliability figure for a 24/7 control panel power bus.

Upstream protection coordination

Recommended miniature circuit breaker for single-phase operation is 10 A characteristic C; for two-phase operation use a 2-pole breaker or Siemens 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V). Maximum I²t value is 9.9 A²·s — the let-through energy the supply can deliver into a fault before the internal protection clears. Typical no-load input current is 0.4 mA; maximum 3.5 mA — low enough that a standard MCB won't nuisance trip on inrush.

Approvals and lifecycle

cULus-Listed under UL 508 and CSA C22.2 No. 107.1, File E197259 — accepted for North American panel builds without additional agency review. CE marked and EAC approved — covers European and Eurasian Economic Union installations.

MPN
6EP1336-3BA00