Skip to main content
Siemens 4EU5021-0AK10-0B

Siemens 4EU5021-0AK10-0B Commutating Choke, 2500 A, 400 V, 5

MPN 4EU5021-0AK10-0B

Siemens 4EU5021-0AK10-0B commutating choke for converter, 3-phase, 2500 A rated current, 400 V AC, 50 Hz, 9.4 µH inductance, 4% relative inductive drop, IP00, thermal class H, UL/CSA recognized.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

4EU5021-0AK10-0B specifications
ParameterValue
IP ratingIP00
Depth0.318 m
Width0.518 m
Height0.565 m

Product details

Commutating choke for converter duty

The Siemens 4EU5021-0AK10-0B is a three-phase commutating choke (Kommutierungsdrossel) designed for converter applications. It carries a rated current of 2500 A at 400 V AC, 50 Hz, with a rated inductance of 9.4 µH and a relative inductive voltage drop of 4% at the measurement level. The 2500 A rating is the continuous thermal current (Ithmax) — the choke is sized for the full converter output, not a derated branch.

Thermal class H and IP00 — what they mean for installation

Thermal class H per IEC 60085 means the insulation system is rated for a 180 °C hot-spot temperature, which is necessary for high-current chokes where copper losses (1650 W in the coil) and iron losses (300 W) add up. The IP00 protection class means the choke has no enclosure — it is an open-frame component intended for mounting inside a switchgear cabinet or converter cubicle where personnel access is restricted. The flat-type terminals (flat connector) are sized for the 2500 A busbar connection; expect bolted joints with proper torque.

Physical dimensions and panel fit

The choke measures 0.565 m high, 0.518 m wide, and 0.318 m deep. At roughly half a meter per side, it requires a dedicated mounting footprint inside the cabinet — not a DIN-rail component. Verify the enclosure depth and busbar access before specifying; the flat-type terminals need clearance for bolted connections.

MPN
4EU5021-0AK10-0B