Skip to main content
Siemens 6EP3124-0TA00-0AY0

Siemens 6EP3124-0TA00-0AY0 Power Supply, 15 A, 24 VDC, DIN R

MPN 6EP3124-0TA00-0AY0
Active

Siemens SITOP PSU8200, 6EP3124-0TA00-0AY0, 24 V DC / 15 A, DIN rail mount, 91% efficiency, IP20.

$244.98 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6EP3124-0TA00-0AY0 specifications
ParameterValue
Fuse protection type25 A (not accessible), breaking capacity 300 A
Voltage12 V
Power200 W
IP ratingIP20
MountingSnaps onto DIN rail EN 60715 35x7.5/15
Depth120 mm
Width42 mm
Height125 mm
Efficiency91%

Product details

The Siemens 6EP3124-0TA00-0AY0 is a 24 V DC switched-mode power supply rated for 15 A continuous, with a typical output of 16 A. It delivers 91% efficiency at rated load, which keeps heat dissipation low in a crowded cabinet. The input accepts 14 to 32 V DC, so it works on nominal 24 V battery-backed or rectified DC buses without a separate input module. Mounting is standard DIN rail per EN 60715 (35×7.5/15). Clearance of 50 mm above and below the unit is required for natural convection cooling; the side gaps can be zero. The output is galvanically isolated and SELV-rated per EN 60950-1, so it is safe for powering PLCs, I/O racks, sensors, and other 24 V control loads in industrial and commercial panels. The unit is also approved for shipboard use (ABS, DNV GL), which extends its suitability to marine and offshore installations.

Ratings That Drive the Selection

Between +60 °C and +70 °C ambient, the output must be reduced by 2% per Kelvin. At +65 °C, for example, the usable current drops to about 13.5 A. If the panel runs hot, size up or add forced air. Startup is guaranteed from 18 V DC, with derated operation possible down to 14 V DC. This is useful for battery-backed systems where the bus voltage sags under load. The inrush current is limited to an I²t of 0.6 A²·s, which prevents nuisance tripping of upstream breakers. The recommended upstream protection is a 16 A miniature circuit breaker, characteristic B or C. The unit itself has an internal non-accessible 25 A fuse with a breaking capacity of 300 A, so it can handle a hard output short without cascading.

Approvals include cULus (UL 508, CSA C22.2 No. 107.1), CE, EAC, and DNV GL. The UL file number is E197259. No ATEX or IECEx certification — this is not a hazardous-location power supply. For a standard control panel or marine installation, the existing approvals cover the regulatory scope.

Terminal and Wiring Notes

Output terminals (+, -) are also screw terminals, same wire range. A separate signaling contact terminal block is provided for remote monitoring. All terminals are sized for standard panel wiring; no special tools needed. The unit can be bridged with a buffer module if ride-through during line dips is required. That is an accessory, not included, but the capability is built into the design.

MPN
6EP3124-0TA00-0AY0