What this RCBO does in the panel
The integrated earth-leakage protection trips at 30 mA sensitivity, covering personnel protection against indirect contact per IEC 60364. Breaking capacity is 4500 A Icn at 230…240 V AC, 50 Hz, certified to EN/IEC 61009-2-1 — adequate for domestic and light commercial final circuits where the prospective fault current stays under that level.
Clip-on mounting to DIN rail (35 mm per EN 60715). The 9 mm connection pitch between phase and neutral matches the Acti9 busbar system. Terminals accept 1…16 mm² rigid or 1…10 mm² flexible cable; strip length is 15 mm, tightening torque 2 N·m. IP20 on the body, IP40 inside the modular enclosure — install inside a cabinet, not exposed to washdown.