Skip to main content
Schneider Electric A9D54210

Schneider Electric A9D54210 Acti9 iC60 RCBO, 10 A, 2P, 300 m

MPN A9D54210
Active

Schneider Electric Acti9 iC60 RCBO, 2P, 10 A, C curve, 300 mA earth-leakage, 10 kA Icn, DIN-rail clip-on.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9D54210 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage220...240 V AC 50 Hz
Insulation voltage ui500 V AC 50 Hz
Breaking capacity10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2
Terminal pitch9 mm between poles
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
ColorWhite

All specifications

A9D54210 additional specifications
ParameterValue
Depth78 mm
Width36 mm
Height86 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9D54210 is an Acti9 iC60 RCBO — a combined 2-pole residual-current circuit breaker with overcurrent protection, rated 10 A with a C curve and 300 mA earth-leakage sensitivity.

Breaking capacity is 10 kA Icn at 230 V per EN/IEC 61009-2-1, with an ultimate breaking capacity Icu of 15 kA per EN/IEC 60947-2. That Icu figure tells you the device can safely interrupt a fault once at the higher level — useful for coordination studies where the upstream device clears faster. The C curve trips magnetically between 5 and 10 times In, so for a 10 A RCBO that means instantaneous trip between 50 A and 100 A, typical for general-purpose distribution with moderate inrush (lighting, small motor starters). Earth-leakage protection is integrated at 300 mA sensitivity, covering both poles. The 300 mA threshold is common for protection against fire risk in circuits supplying fixed equipment, not for personal shock protection (which would require 30 mA). Thermal-magnetic trip unit gives you the standard bimetal overload protection plus a solenoid for short-circuits.

Strip length 12 mm for top or bottom connection; tightening torque 2 N·m.

MPN
A9D54210