The Schneider Electric A9D51216 is an Acti9 iC60H2 RCBO — a residual current breaker with overcurrent protection, combining a 2-pole MCB and a 300 mA earth-leakage module in one 36 mm wide DIN-rail unit. Integrated earth-leakage protection at 300 mA sensitivity catches insulation faults before they become line-to-ground arcs; the thermal-magnetic trip handles the overcurrent side.
Neutral on the left. Screw-clamp terminals: top accepts 1–25 mm² rigid or 1–16 mm² flexible; bottom accepts 1–16 mm² rigid or 1–10 mm² flexible. Tightening torque 3.5 N·m top, 2 N·m bottom. Strip length 14 mm top, 13 mm bottom. IP20 finger-safe front; intended for enclosure mounting where the live terminals are behind a panel door. Padlockable with a Ø 4 mm padlock for lockout/tagout.