Skip to main content
Schneider Electric A9D71810 — Residual Current Breakers (RCCB/RCBO)

Schneider A9D71810 iC60N RCBO, 10 A D-curve, 30 mA, 6 kA

MPNA9D71810
Active

Schneider Acti9 iC60N RCBO, 1P+N, 10 A rated current, D-curve, 30 mA earth leakage, 6 kA breaking capacity, DIN-rail clip-on, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D71810 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D71810 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D71810 — Identification
ParameterValue
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60N RCBO
A9D71810 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D71810 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D71810 — Approvals
ParameterValue
StandardsBS EN 61009-1 IEC 61009-1 IEC 61009-2-2 AS/NZS 61009.1

Product details

It protects a single-phase outgoing circuit (1P + Ns, neutral on the left) with a thermal-magnetic trip unit rated 10 A at 50 °C and a built-in 30 mA earth-leakage sensor.

Clip-on mounting on a standard 45 mm grid DIN rail, occupying 2 x 9 mm pitches (18 mm total). The 77.5 mm depth and 110 mm height fit within a standard distribution board or sub-panel enclosure. Screw-clamp terminals: top accepts up to 25 mm² rigid, bottom up to 16 mm² rigid; torque to 3.5 N·m on the top connection, 2 N·m on the bottom. Strip lengths are 14 mm (top) and 13 mm (bottom). IP20 finger-safe for panel use, not for wet locations.

Frequently asked questions

What is the breaking capacity of A9D71810?

The breaking capacity is 6000 A Icn at 230/240 V AC, 50/60 Hz. Limitation class 3 helps reduce let-through energy on faults.

What does the D-curve mean for this RCBO?

The D-curve trips between 10 and 20 times the rated current (100–200 A for this 10 A unit), designed for loads with high inrush like small motors, transformers, or solenoid banks.

How do I get pricing and availability for A9D71810?

The A9D71810 is sourced to order against an RFQ. Submit a request for quote to confirm current pricing and availability through independent distribution.

What standards does A9D71810 comply with?

It complies with BS EN 61009-1, IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1.

MPN