The integrated 30 mA earth-leakage protection covers personnel and fire risk in TN earthing systems. Breaking capacity is 6000 A Icn at 230/240 V AC, 50/60 Hz, which suits most residential and light-commercial final circuits in markets that follow IEC 61009-1 or BS EN 61009-1.
Screw-clamp terminals: top accepts 1…25 mm² rigid (1…16 mm² flexible), bottom accepts 1…16 mm² rigid (1…10 mm² flexible). Torque to 3.5 N·m top, 2 N·m bottom. IP20 rated — suitable for dry indoor enclosures only. The white housing and toggle ON/OFF indication give clear visual status.
For compliance documentation, the unit carries approvals to BS EN 61009-1, IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1. It is suitable for isolation (marked accordingly). If you need a specific declaration (RoHS, REACH, UL), request it with your RFQ — those are typically available from the manufacturer but not embedded in the product label.