Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 10 A, C-curve, 100 mA earth leakage, 6 kA Icn, clip-on DIN rail, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D72610 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A-G
Earth-leakage trip time delayDelayed
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D72610 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D72610 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D72610 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D72610 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D72610 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D72610 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — a single-module device combining a 10 A thermal-magnetic MCB and a 100 mA earth-leakage detector in one 1P+N package. The C-curve (magnetic trip 5–10 x In) means it handles moderate inrush from small motors or lighting ballasts without nuisance tripping, while the 100 mA sensitivity catches ground faults on circuits where 30 mA would be too tight for leakage from long cable runs or industrial heaters. Breaking capacity is 6 kA Icn at 230 V AC per EN/IEC 61009-2-1 — enough for most final subcircuits in a distribution board where the upstream device limits fault current. The limitation class 3 rating means it lets through less energy during a short-circuit than a standard breaker, which helps with downstream equipment protection.

Clip-on mounting on DIN rail, 36 mm wide (4 x 9 mm pitches), neutral on the left. The 73 mm depth leaves clearance behind a standard 100 mm deep enclosure. Terminals accept up to 16 mm² rigid or 10 mm² flexible, with a 2 N.m torque spec and 15 mm strip length — standard for a 10 A device. IP20 on the body, IP40 inside a modular enclosure; pollution degree 3 means it's rated for industrial environments where conductive dust or condensation is present.

Frequently asked questions

Who supplies A9D72610 and how is it quoted for volume purchases?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery requirements.

What is the closest alternative to A9D72610 in the Acti9 family?

Within the Acti9 iDPN Vigi range, the main variant difference is the earth-leakage sensitivity — this unit is 100 mA, while a 30 mA version (different order code) exists for circuits requiring personnel protection. The 10 A C-curve and 6 kA breaking capacity are shared across both. Pin-compatible in the same 1P+N form factor.

What compliance documentation does Schneider provide for A9D72610?

The device is certified to EN/IEC 61009-2-1 for RCBOs and carries tropicalisation class 2 per IEC 60068-1. Standard Schneider documentation includes the CE declaration of conformity and RoHS/REACH compliance statements available through their product documentation portal.