It protects a single-phase outgoing circuit at 6 A rated current (C-curve, magnetic trip 5–10×In) and integrates earth-leakage detection at 100 mA sensitivity. The thermal-magnetic trip handles overloads and short-circuits; the residual-current element covers ground faults without a separate RCCB upstream. Breaking capacity is 6000 A Icn at 220–240 V AC, 50 Hz, per EN/IEC 61009-2-1.
Clip-on DIN rail mount, 36 mm wide (4 × 9 mm pitches), neutral on the left. The single-pole + neutral format saves one module width versus a two-pole MCB plus separate RCCB — useful when panel space is tight. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip length 15 mm, torque to 2 N·m. IP20 on the device body, IP40 inside a modular enclosure.
Limitation class 3 — energy-limiting performance that reduces let-through energy on short-circuits. Tropicalisation level 2 per IEC 60068-1 (damp heat, 95 % RH at 55 °C).