Skip to main content
Schneider Electric A9R75440 — Residual Current Breakers (RCCB/RCBO)

A9R75440 Acti9 iID K RCCB, 40 A, 300 mA, 4P

MPNA9R75440
Active

Schneider Electric Acti9 iID K, residual current circuit breaker (RCCB), 4P, 40 A, 300 mA sensitivity, Type AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R75440 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R75440 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9R75440 — Identification
ParameterValue
Product nameActi9 iID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID K
A9R75440 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminals top or bottom 1...35 mm² rigid Tunnel type terminals top or bottom 1...25 mm² flexible Tunnel type terminals top or bottom 1...25 mm² flexible with ferrule
Wire stripping length16 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height85 mm
Depth69 mm
A9R75440 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9R75440 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9R75440 is a 4-pole residual current circuit breaker (RCCB) from the Acti9 iID K series, rated at 40 A with 300 mA earth-leakage sensitivity. The part clips onto a DIN rail (mounting support: DIN rail, clip-on) and fits an 8-module width (72 mm). Current-production status is confirmed.

The 300 mA sensitivity suits fire-protection or general-purpose earth-leakage protection where personnel shock protection is not required.

The neutral position is on the left.

Frequently asked questions

What is A9R75440's listed range (Acti9) on this component line?

It belongs to the Acti9 range, specifically the iID K series of residual current circuit breakers.

MPN
A9R75440