It combines a 6 A thermal-magnetic MCB (C-curve, 5–10 x In magnetic trip) with integrated earth-leakage detection in a single 36 mm wide module that clips onto a DIN rail.
The 6 A rated current (In) and C-curve mean this RCBO is sized for lighting circuits, small appliance loads, or control transformers — not motor or high-inrush loads. The C-curve's 5–10 x In magnetic trip window (30–60 A instantaneous) avoids nuisance trips on moderate inrush but still clears a hard fault fast. The integrated earth-leakage protection (no separate RCCB) saves panel space and wiring time, but the neutral is fixed on the left — verify your busbar or feed arrangement before landing the module.
Cable entry from top or bottom. IP20 finger-safe front, pollution degree 2 — standard for enclosed distribution boards. Tropicalisation severity B (28-day damp heat per IEC 60068-2-30) means it holds up in high-humidity environments without derating.