Rated breaking capacity is 6 kA at 240 V AC, 50 Hz, per AS/NZS 61009.1.
Neutral on the left, cable entry top and bottom. Tightening torque 2 N·m; strip length 14 mm. IP20 finger-safe front, pollution degree 2 — standard for enclosed distribution boards. Tropicalisation severity B per IEC 60068-2-30 (28-day damp heat cycle) means it holds up in coastal or high-humidity plant rooms without derating.