It carries a 25 A rated current with a C-curve magnetic trip (5 to 10 x In) and a 6 kA breaking capacity at 240 V AC, 50 Hz, tested to EN/IEC 62606 and AS/NZS 61009.1. The integrated earth-leakage protection means you get both short-circuit/overload and residual-current protection in one DIN-rail unit, saving panel space and wiring time.
Clip-on mounting to a standard DIN rail, 36 mm wide (2 modular spaces), 91 mm tall, 75 mm deep.
Electrical durability 10,000 cycles, mechanical 20,000 cycles. Power loss 6.5 W per pole. Tropicalisation severity B per IEC 60068-2-30 for 28 days. Limitation class 3 per AS/NZS 61009.1 — meaning it lets through limited energy under fault, which helps with downstream coordination.