Schneider Electric A9Z01240 — Residual Current Breakers (RCCB/RCBO)

Schneider A9Z01240 RCCB, 40A 30mA Type A

MPNA9Z01240
Active

Schneider Electric Acti9 ID K A9Z01240 residual current circuit breaker, 2P, 40 A, 30 mA, Type A, 220-240 V AC.

$42.39Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z01240 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z01240 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9Z01240 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9Z01240 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth68 mm
A9Z01240 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9Z01240 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

Integrator’s quick read

It trips on earth leakage down to 30 mA, covers sinusoidal and pulsed DC fault currents, and does it without relying on the supply voltage—the voltage-independent mechanism means it clears an earth fault even if the neutral is lost upstream. Connections accept up to 35 mm² rigid or 25 mm² flexible via the top or bottom biconnect terminals; tighten to 3.5 N·m and strip 14 mm. Pollution degree 2, IP20 (IP40 inside a modular enclosure), and it's designed for the standard 50/60 Hz network. The earth-leakage protection is instantaneous—no time delay.

Mounting & wiring notes

Neutral fixed left—plan your busbar/finger alignment accordingly. Terminals accept rigid conductors 1–35 mm² or flexible 1–25 mm² top and bottom. If paralleling conductors, sum cross-sections must stay within terminal capacity—no daisy-chaining through the RCCB itself. Operational temperature range -25 to 40 °C; storage -30 to 70 °C. The IP20 face is sufficient for distribution boards; the IP40 modular enclosure rating applies when panel front is closed.

Frequently asked questions

What is the depth of A9Z01240?

The depth is 68 mm.

What range does A9Z01240 belong to?

It belongs to the Acti9 range.

What compliance documentation is available for A9Z01240?

The device is certified to EN/IEC 61008-1 and EN/IEC 61008-2-1 and carries the VDE quality label.

MPN