Skip to main content
Schneider Electric A9Z03240 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z03240 Acti9 ID K RCCB, 40 A, 300 mA, T

MPNA9Z03240
Active

Schneider Electric Acti9 ID K, RCCB, 40 A, 300 mA, Type A, 2P, DIN rail, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z03240 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z03240 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9Z03240 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9Z03240 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth68 mm
A9Z03240 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9Z03240 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

Rated 40 A continuous at 220…240 V AC, 50/60 Hz, it is sized for outgoing submain or feeder protection in a distribution board.

Clip-on mount to DIN rail, 36 mm wide (4 x 9 mm pitches), 81 mm tall, 68 mm deep. Neutral on the left. Biconnect terminals accept 1…35 mm² rigid or 1…25 mm² flexible; strip 14 mm, torque to 3.5 N·m. IP20 body, IP40 inside a modular enclosure — standard for panelboard installation, not for wet-area standalone use.

The Acti9 ID K range is an established Schneider line, so BOM continuity is stable.

Frequently asked questions

What are the key ratings of A9Z03240?

40 A rated current, 300 mA earth-leakage sensitivity, Type A (AC and pulsating DC), 2-pole, rated operational voltage 220…240 V AC, instantaneous trip, voltage-independent tripping technology.

Where can I buy A9Z03240?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What standards does A9Z03240 comply with?

It complies with EN/IEC 61008-1 and EN/IEC 61008-2-1, carries VDE quality label, and is rated IP20 (IP40 in modular enclosure).

MPN
A9Z03240