Skip to main content
Schneider Electric C063B4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C063B4WM ComPacT NS630bLB Frame, 630A 4P

MPNC063B4WM
Active

Schneider Electric ComPacT NS630bLB new generation, basic frame, 630 A at 50 °C, 4P, withdrawable, manually operated, 200 kA Icu at 415 V AC, IEC 60947-2.

$6,920.64Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063B4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C063B4WM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to EN 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to EN 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to EN 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C063B4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C063B4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C063B4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C063B4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric C063B4WM is a ComPacT NS630bLB new-generation basic frame — a 4-pole, withdrawable, manually operated air circuit breaker rated 630 A at 50 °C. It ships without a control unit or protection module, so you fit the trip unit that matches your distribution scheme (Micrologic or otherwise). At 690 V AC the Icu still holds at 75 kA, which covers most industrial step-down transformer secondaries.

At 690 V AC the Icu is 75 kA, still well above most 690 V distribution fault levels. The Icw (rated short-time withstand current) is 19.2 kA for 1 second, which matters for selective coordination downstream: the frame can hold a fault current long enough for a feeder breaker to clear first.

Withdrawable mounting — panel integration

This is a withdrawable frame, meaning the moving portion (the breaker itself) slides out of a fixed cradle for inspection or swap without disturbing the bus connections. Mounts on a backplate with a 70 mm connection pitch. Dimensions are 306 mm wide × 260 mm high × 147 mm deep — that's a compact footprint for a 630 A frame, so it fits in standard switchgear cubicles without needing a deep enclosure. IP40 front face protection keeps tools and fingers out; IK07 impact rating means it survives the odd dropped screwdriver during commissioning.

Durability and environmental range

Mechanical durability is 10,000 cycles per IEC 60947-2 — that's the expected life of the mechanism before maintenance. Electrical durability varies with voltage and current: 2,000 cycles at 690 V AC at rated In, up to 4,000 cycles at 440 V AC at In/2.

Frequently asked questions

What breaking capacity does C063B4WM have at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The Ics (service breaking capacity) is the same 200 kA at that voltage, so the frame can be reclosed after a full fault without derating.

Does this frame come with a trip unit or protection module?

No — this is a basic frame (product type 'Basic frame' per the spec), shipped without a control unit. You select and fit the appropriate Micrologic or other trip unit separately.

What is the closest alternative to C063B4WM in the same family?

Within the ComPacT NS630b...1600 range, the fixed-mount version (non-withdrawable) shares the same 630 A rating and 200 kA breaking capacity but bolts directly to the backplate instead of sliding into a cradle. The withdrawable version gives you faster swap-out without disturbing bus connections — choose based on whether uptime during maintenance justifies the cradle cost.

Where can I buy C063B4WM and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
C063B4WM