Schneider Electric C063H4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H4WM ComPacT NS630bH Basic Frame, 630

MPNC063H4WM
Active

Schneider Electric ComPacT NS630bH new generation, basic frame C063H4WM, 630 A, 4 poles, withdrawable, manually operated, 70 kA Icu at 415 V AC.

$5,252.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C063H4WM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C063H4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C063H4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C063H4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The C063H4WM is a basic frame for the Schneider Electric ComPacT NS630bH new generation — a 4-pole, 630 A air circuit breaker chassis designed for distribution duty in IEC 60947-2 environments. It ships as a manually operated, withdrawable unit without a protection control unit, meaning you select and install the trip unit separately to match your coordination study. At 690 V AC the Icu still holds at 42 kA, so it handles industrial supply voltages without derating the interrupting rating below what most plant networks need. The 630 A rating at 50 °C ambient means you can load it to nameplate in a warm enclosure — no derating curve to chase for typical panel temperatures. Withdrawable mounting (backplate, 70 mm pitch) means the chassis slides out for inspection or swap without disconnecting the main busbars, which cuts downtime on a live-panel retrofit.

Breaking capacity profile across voltages

The H rating delivers 85 kA Icu at 240 V, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 525 V, and 42 kA at 690 V. The corresponding Ics (service breaking capacity) — the level the breaker can clear and still be switched back on — is 50 kA from 240 V through 440 V, then 40 kA at 525 V and 30 kA at 690 V. For a 400 V panel, the 70 kA Icu / 50 kA Ics combination gives full selectivity headroom against a downstream 50 kA-rated MCCB without forcing a larger upstream device.

The C063H4WM is a current-production item in Schneider's ComPacT NS630b...1600 new generation range.

Mechanical and electrical endurance

Rated for 10,000 mechanical cycles and up to 6,000 electrical cycles at 440 V at rated current (In), or 4,000 cycles at 690 V. At half-rated current (In/2), electrical durability extends to 6,000 cycles at 440 V and 4,000 cycles at 690 V. For a distribution board that sees a few operations per week, this endurance covers the life of the installation without contact maintenance.

IP40 front-face protection (IK07 impact resistance) suits indoor switchgear enclosures — not washdown, but fine for a dry electrical room. Neutral is on the left; connection pitch is 70 mm. Power dissipation at rated current is 19 W — negligible for panel thermal calculations but worth noting if the enclosure is densely packed.

Frequently asked questions

Where can I buy C063H4WM and how do I get a price?

The C063H4WM is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is C063H4WM's breaking capacity at 415 V?

The C063H4WM carries an Icu of 70 kA at 380/415 V AC and an Ics of 50 kA at the same voltage, both per IEC 60947-2.

What compliance standards does C063H4WM meet?

The C063H4WM is designed to IEC 60947-2, with a rated insulation voltage of 800 V AC, impulse withstand of 8 kV, and overvoltage category III. It is isolation-rated per EN/IEC 60947-2 and carries IP40 and IK07 protection ratings.

MPN
C063H4WM