Skip to main content
Schneider Electric C063H4FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H4FM ComPacT NS630bH, 630A 4P, 70kA a

MPNC063H4FM
Active

Schneider Electric ComPacT NS630bH new generation, C063H4FM, basic frame, 630A at 50°C, 4P, fixed, manually operated, 70 kA Icu at 415 V AC, without control unit.

$1,907.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H4FM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C063H4FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H4FM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C063H4FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C063H4FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C063H4FM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What this frame is — and what it isn't

The C063H4FM is a Schneider Electric ComPacT NS630bH new generation basic frame — a 4-pole, fixed-mount, manually operated circuit breaker frame rated 630 A at 50 °C. It carries a 70 kA Icu at 415 V AC (85 kA at 240 V, 42 kA at 690 V) and is built to IEC 60947-2 (Category B, pollution degree 3). The key distinction: this is the bare frame only, without a protection control unit or any integral trip module. You spec the trip unit separately to match your distribution or motor protection curve.

At 690 V AC the Icu drops to 42 kA, with Ics at 30 kA. For selectivity studies, the rated short-time withstand current (Icw) is 19.2 kA for 1 second — enough to coordinate with downstream breakers in a distribution panel.

Fixed-mount on a backplate (connection pitch 70 mm). Dimensions: 280 mm wide, 224 mm high, 147 mm deep. IP40 front face protection (IK07 impact resistance) suits it for indoor panel installation where dust ingress is limited. The front face is Class II shock-protected.

Frequently asked questions

How do I get current pricing and availability for C063H4FM?

Submit an RFQ through this listing. The C063H4FM is sourced to order via independent distribution, and current pricing and availability are confirmed at quote time.

What is C063H4FM's breaking capacity at 415 V AC?

The C063H4FM has a 70 kA Icu (ultimate breaking capacity) at 380/415 V AC 50/60 Hz per IEC 60947-2, with a 50 kA Ics (service breaking capacity) at the same voltage.

Does the C063H4FM include a trip unit?

No. The C063H4FM is a basic frame only — it ships without a protection control unit. You must select and install a compatible trip unit separately to define the protection curve.

What standards does the C063H4FM comply with?

It is designed and tested to IEC 60947-2 (low-voltage switchgear and controlgear — circuit breakers), with pollution degree 3, overvoltage category III, and suitability for isolation per EN/IEC 60947-2.

MPN