Skip to main content
Schneider Electric C063H42AFM — Miniature Circuit Breakers (MCB)

C063H42AFM ComPacT NS 630A 4P 85kA MCCB, MicroLogic 2.0 A

MPNC063H42AFM
Active

Schneider Electric ComPacT NS new generation, C063H42AFM, 4P 630 A MCCB, MicroLogic 2.0 A electronic trip unit, 85 kA Icu at 240 V AC, fixed mount, front connections.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H42AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H42AFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H42AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H42AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H42AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H42AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H42AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

630 A distribution MCCB with MicroLogic 2.0 A

The C063H42AFM is a Schneider Electric ComPacT NS new generation 4-pole moulded-case circuit breaker rated 630 A at 50 °C, fitted with a MicroLogic 2.0 A electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection. Its 85 kA Icu at 220/240 V AC (70 kA at 415 V, 65 kA at 440 V, 50 kA at 500/525 V, 42 kA at 690 V) per IEC 60947-2 makes it suitable for high-fault distribution panels where the available short-circuit current is substantial. The fixed-mount, front-connection design with a 70 mm connection pitch and backplate mounting support simplifies panel layout for a 280 × 327 × 147 mm footprint.

The MicroLogic 2.0 A electronic trip unit gives adjustable long-time pickup and delay plus fixed instantaneous pickup, with a 20-minute thermal memory that prevents nuisance reclose after a hot overload. Category B utilisation means it is fully rated for selectivity with downstream breakers — the integrator can coordinate time-current curves without sacrificing upstream protection.

Fixed-mount on a backplate with front connections both top and bottom — wire entry and exit are on the same face, which simplifies busbar routing in a vertical section. IP40 enclosure protection (IK07 impact) means it is suited for indoor switchgear but not washdown environments. The LCD display and four red LEDs (fault) plus one yellow LED (overload) give local status without opening the door. Neutral is on the left in the 4-pole configuration.

Frequently asked questions

What are the key ratings of C063H42AFM?

630 A at 50 °C, 4 poles, MicroLogic 2.0 A electronic trip unit with L and I protection, breaking capacity 85 kA Icu at 240 V AC (70 kA at 415 V, 65 kA at 440 V, 50 kA at 500/525 V, 42 kA at 690 V) per IEC 60947-2.

MPN