C063H42EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H42EFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H42EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H42EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H42EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H42EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H42EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C063H42EFM is a ComPacT NS new generation 4-pole fixed circuit breaker rated 630 A at 50 °C, with a MicroLogic 2.0 E electronic trip unit providing overload (L) and instantaneous short-circuit (I) protection. It is built to EN/IEC 60947-2 and carries a breaking capacity of 85 kA Icu at 220/240 V AC, 70 kA at 380/415 V, and 65 kA at 440 V — numbers that govern its use as a main or feeder breaker in distribution switchboards where high fault current is expected.

The 630 A trip unit rating at 50 °C sets the continuous current limit; above that ambient, derating applies per IEC 60947-2. The MicroLogic 2.0 E electronic trip unit includes thermal memory (20 minutes), which prevents nuisance tripping on repeated overloads by tracking the conductor temperature. Mechanical durability is rated at 10,000 cycles; electrical durability varies with load: 2,000 cycles at 690 V In, 5,000 at 440 V In. That matters for applications where the breaker is used as a manual disconnect under load.

Dimensions are 327 mm high, 280 mm wide, 147 mm deep — panel builders should verify cutout and clearance for the 4-pole width. IP40 enclosure protection (IK07 impact) suits indoor distribution boards; not rated for washdown.

Frequently asked questions

What is the breaking capacity of C063H42EFM?

85 kA Icu at 220/240 V AC, 70 kA at 380/415 V, 65 kA at 440 V, 50 kA at 500/525 V, and 42 kA at 660/690 V AC, all per IEC 60947-2.

What trip unit does C063H42EFM use?

A MicroLogic 2.0 E electronic trip unit with L (overload) and I (instantaneous short-circuit) protection, plus 20-minute thermal memory.

Where can I buy C063H42EFM and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN