Skip to main content
Schneider Electric C063H45EFM — Miniature Circuit Breakers (MCB)

Schneider Electric C063H45EFM ComPacT NS 630A, 70kA 415V AC

MPNC063H45EFM
Active

Schneider Electric ComPacT NS new generation, C063H45EFM, 4P MCCB, 630 A, 70 kA Icu at 415 V AC, MicroLogic 5.0 E electronic trip unit, fixed mount, front connection.

$3,337.34Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063H45EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063H45EFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C063H45EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063H45EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063H45EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063H45EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063H45EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C063H45EFM is a ComPacT NS new generation 4-pole moulded-case circuit breaker rated 630 A at 50 °C, with a MicroLogic 5.0 E electronic trip unit. The 5.0 E adds energy-metering capability — it measures real-time consumption, not just trips, so you can pull load profiles off the breaker without a separate power meter. That saves a DIN-rail slot and a Modbus node if you're already reading the breaker via the communication bus. For a 630 A main on a 415 V distribution board, that covers most utility-transformer fault levels. The trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves. The S curve is adjustable with a time delay, so you can coordinate downstream breakers — essential for selective coordination in a multi-level distribution panel. Thermal memory is 20 minutes, meaning the breaker remembers a prior overload and shortens the trip time on a repeat event, which protects cables from cumulative heating.

Mounting and integration — fixed, front-connected, backplate-mounted

That means all terminations are accessible from the front of the panel — no rear bus work, no need to reach behind the breaker. Mounting is on a backplate, not a DIN rail, so plan for a drilled and tapped mounting surface. Dimensions are 327 mm high × 280 mm wide × 147 mm deep. Local signalling uses four red LEDs for fault indication and one yellow LED for overload. The LCD display on the MicroLogic 5.0 E shows real-time current, energy, and trip-event data — no need to plug in a laptop to see what caused a trip. That's a time-saver for maintenance: walk up, read the display, reset, and log the event.

Lifecycle and sourcing — active production, standard availability

Overvoltage category III confirms it's suitable for fixed-installation distribution boards, not just downstream equipment.

Frequently asked questions

What is C063H45EFM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. The H suffix in the order code indicates this 70 kA rating level.

What protection curves does the MicroLogic 5.0 E trip unit provide?

L (long-time overload), S (short-time short-circuit with adjustable delay), and I (instantaneous short-circuit) protection. The S curve allows selective coordination with downstream breakers.

Where can I buy C063H45EFM?

The C063H45EFM is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the closest alternative to C063H45EFM in the ComPacT family?

Within the ComPacT NS new generation, the closest alternative would be a breaker with a different trip unit rating or breaking capacity code. The C063H45EFM is the 630 A, 70 kA at 415 V variant with MicroLogic 5.0 E. A lower or higher current rating or a different trip unit (e.g., MicroLogic 2.0 without energy metering) would change the order code. No pin-compatible drop-in exists with a different rating — the trip unit and frame are matched.

MPN
C063H45EFM