Skip to main content
Schneider Electric C063L350FM — Miniature Circuit Breakers (MCB)

C063L350FM ComPacT NS630b-1600, 630A, 150kA 415V AC

MPNC063L350FM
Active

Schneider Electric ComPacT NS new generation, C063L350FM, 3P, 630 A at 50 °C, MicroLogic 5.0 electronic trip unit, 150 kA Icu at 415 V AC, fixed mount, backplate.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063L350FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063L350FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C063L350FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063L350FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063L350FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063L350FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063L350FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

It's a 3-pole, 630 A frame with a MicroLogic 5.0 electronic trip unit providing LSI protection — long-time overload, short-time short-circuit, and instantaneous short-circuit.

If your enclosure runs hotter, you'll need to consult the thermal derating curve — but for most industrial switchboards, 630 A covers a large motor control center feeder or a transformer secondary. The MicroLogic 5.0 is electronic, so it gives you adjustable long-time, short-time, and instantaneous pickup settings, plus a 20-minute thermal memory that prevents nuisance tripping on repeated overloads. The IP40 front face and IK07 impact resistance are adequate for enclosed panel mounting; it's not rated for washdown environments.

Fixed mount on a backplate — no draw-out cradle. The 210 mm width, 327 mm height, and 147 mm depth fit standard switchboard cubicle compartments. The manually operated control type means no motor operator or shunt trip is included; those are add-on accessories. Four red LEDs for fault indication and one yellow for overload give local status without opening the door.

Frequently asked questions

How do I get current pricing and availability for C063L350FM?

Submit an RFQ through the storefront. Pricing and stock are confirmed at quote time through independent distribution channels; the part is sourced to order.

What is C063L350FM's breaking capacity at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the maximum short-circuit current it can safely interrupt at typical 400 V distribution levels.

What trip unit does C063L350FM use?

A MicroLogic 5.0 electronic trip unit with LSI protection: long-time overload, short-time short-circuit, and instantaneous short-circuit. It has a 20-minute thermal memory.

What are the mounting dimensions for C063L350FM?

Fixed backplate mount. Width 210 mm, height 327 mm, depth 147 mm. Front connection with 70 mm connection pitch on both line and load sides.