Schneider Electric C063L420FM — Miniature Circuit Breakers (MCB)

Schneider Electric C063L420FM ComPacT NS 630A 4P MCCB, 150 k

MPNC063L420FM
Active

Schneider Electric ComPacT NS new generation, C063L420FM, 4P MCCB, 630 A MicroLogic 2.0 electronic trip unit, 150 kA Icu at 415 V AC, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063L420FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063L420FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C063L420FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063L420FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063L420FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063L420FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063L420FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

What this 630 A MCCB delivers

The Schneider Electric C063L420FM is a ComPacT NS new generation 4-pole moulded-case circuit breaker rated 630 A at 50 °C, fitted with a MicroLogic 2.0 electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection per EN/IEC 60947-2. The electronic trip unit includes a 20-minute thermal memory, so the breaker remembers prior heating and shortens the trip time on a reclose — relevant for motor-starting or repetitive overload applications where nuisance tripping needs to be avoided.

Fixed mounting on a backplate. The 280 mm width, 327 mm height, and 147 mm depth define the enclosure cutout and clearance for front-connection cabling. Connection pitch is 70 mm. IK07 impact rating confirms it withstands a 2 J impact, typical for switchgear enclosures.

Mechanical durability is 10,000 cycles; electrical durability varies by load: 2,000 cycles at 690 V at rated current, 3,000 cycles at 690 V at half-rated current, 3,000 cycles at 440 V at rated current, and 4,000 cycles at 440 V at half-rated current. These figures govern the breaker's service life in a given application — a motor-starting duty with frequent switching will wear the contacts faster than a simple distribution feeder.

Frequently asked questions

What is C063L420FM's breaking capacity at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 130 kA Icu; at 500/525 V it is 100 kA Icu. These are the maximum short-circuit currents the breaker can safely interrupt at those voltages.

What protection does the MicroLogic 2.0 trip unit provide?

L (long-time overload protection) and I (instantaneous short-circuit protection). It is an electronic trip unit with a 20-minute thermal memory. No earth-leakage protection is built in.

What are the mounting dimensions for C063L420FM?

Width 280 mm, height 327 mm, depth 147 mm. Fixed backplate mounting. Connection pitch is 70 mm. Front connection on both upside and downside.

Where can I buy C063L420FM and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN