Skip to main content
Schneider Electric C063L450FM — Miniature Circuit Breakers (MCB)

C063L450FM ComPacT NS 630A 4P Circuit Breaker, 150kA 415V

MPNC063L450FM
Active

Schneider Electric ComPacT NS new generation, C063L450FM, 4P 630A circuit breaker with MicroLogic 5.0 electronic trip unit, 150kA Icu at 415V AC, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063L450FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063L450FM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C063L450FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063L450FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063L450FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063L450FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063L450FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C063L450FM is a Schneider Electric ComPacT NS new generation 4-pole circuit breaker, rated 630 A at 50 °C with a MicroLogic 5.0 electronic trip unit. The electronic trip unit gives you LSI protection curves: long-time overload, short-time short-circuit, and instantaneous short-circuit, plus a 20-minute thermal memory so it doesn't reset its heat history on a fast reclose.

For a 630 A frame, that's a high-interrupting rating, typically specified for large transformer secondaries or heavy industrial feeders where fault current can hit 100 kA+. The 130 kA at 440 V and 100 kA at 500 V tell you the breaker derates as voltage climbs, but it still holds 100 kA at 500 V, which covers most 480 V北美 panels. The MicroLogic 5.0 trip unit is fully electronic, so you get adjustable long-time pickup (Ir), short-time pickup (Isd) with a time delay, and instantaneous (Ii) — no thermal bimetal to drift. The 20-minute thermal memory means if you reclose after a trip, the breaker remembers the prior heat and trips faster on the next overload, which matters for motor starting or capacitor bank switching where repeated inrush can cook the cable.

Panel integration & mounting

Fixed mount on a backplate — no DIN rail on a 630 A frame. Dimensions are 327 mm high, 280 mm wide, 147 mm deep. That's a substantial footprint; plan for a 70 mm connection pitch on the busbars. Front connection both top and bottom, so you can cable it without rear access. IP40 enclosure protection, IK07 impact resistance — fine for a clean indoor switchboard, not for washdown. Neutral is on the left, which matters for busbar phasing if you're paralleling with other breakers.

Frequently asked questions

Where can I buy C063L450FM and how do I get a price?

The C063L450FM is sourced to order against an RFQ through independent distribution. Submit a quote request for current availability and pricing — confirmed at quote time, not from a stock count on a shelf.

What is the closest pin-compatible alternative to C063L450FM in this component family?

Within the ComPacT NS new generation family, the closest alternative would be a different trip unit rating or a 3-pole variant — same frame, same mounting footprint, same breaking capacity class. No exact pin-compatible drop-in exists with a different order code; the trip unit rating and pole count are fixed at order.

What is C063L450FM's listed range (ComPacT) on this component line?

The C063L450FM belongs to the ComPacT NS new generation range, specifically the ComPacT NS630b...1600 new generation product line. It's the 630 A frame size in that family.

What is C063L450FM's listed depth (d) (147 mm) on this component line?

The depth is 147 mm, which is standard for the fixed-mount 630 A frame in the ComPacT NS new generation range. That depth includes the breaker body but not the handle projection or cable bending radius.

What compliance documentation does this brand provide for C063L450FM (RoHS, REACH, UL, IEC)?

The C063L450FM is certified to EN/IEC 60947-2. Schneider Electric typically provides a Declaration of Conformity covering the applicable EU directives. For UL/CSA listings, check the specific variant — the standard ComPacT NS new generation carries IEC ratings; UL versions have a different order code suffix. RoHS and REACH compliance declarations are available from Schneider's documentation portal.

MPN