Skip to main content
Schneider Electric C063L35AFM — Miniature Circuit Breakers (MCB)

C063L35AFM ComPacT NS 630A 3P MCCB, 150 kA at 415V

MPNC063L35AFM
Active

Schneider Electric ComPacT NS new generation, C063L35AFM, 630 A 3P MCCB with MicroLogic 5.0 A electronic trip unit, 150 kA Icu at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063L35AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C063L35AFM — Ratings
ParameterValue
Rated current (In)630 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C063L35AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C063L35AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C063L35AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C063L35AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C063L35AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C063L35AFM is a Schneider Electric ComPacT NS new generation 3-pole molded-case circuit breaker rated 630 A at 50 °C, fitted with a MicroLogic 5.0 A electronic trip unit. It's built for distribution duty in fixed-mount, manually operated panels — the backplate mount and 70 mm connection pitch make it a straight swap into existing ComPacT NS630b to 1600 switchboards.

For selectivity with downstream breakers, the MicroLogic 5.0 A provides LSI protection curves: overload (L), short-time short-circuit (S), and instantaneous (I). The 20-minute thermal memory means the trip unit remembers prior heating events, so it won't nuisance-trip on repeated inrush if the breaker is still warm. Category A utilization (no intentional short-time delay) confirms this is for distribution, not motor-starting duty.

Integration notes

Fixed mount on a backplate, 210 mm wide, 327 mm tall, 147 mm deep — fits standard ComPacT cutouts. Front connection both top and bottom; connection pitch is 70 mm. The LCD display and four red LEDs for fault indication plus one yellow for overload give you on-board diagnostics without a separate meter. IK07 impact resistance handles accidental tool drops during maintenance.

Frequently asked questions

Where can I buy C063L35AFM and get a price?

C063L35AFM is available to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of C063L35AFM at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2.

What trip unit does C063L35AFM use?

MicroLogic 5.0 A electronic trip unit with LSI protection (overload, short-time short-circuit, instantaneous) and 20-minute thermal memory.

What standards does C063L35AFM comply with?

EN/IEC 60947-2, pollution degree 3, overvoltage category III, IP40, IK07.

MPN