Skip to main content
Schneider Electric C063S3WM — Miniature Circuit Breakers (MCB)

C063S3WM ComPacT NS Switch Disconnector, 630A, 3P, Withdrawa

MPNC063S3WM
Active

Schneider Electric ComPacT NS new generation, basic frame switch disconnector, C063S3WM, 3P, 630 A, withdrawable, manually operated, 690 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C063S3WM — Identification
ParameterValue
Product nameComPacT NS new generation
Product/component typeBasic frame
Device applicationDistribution
C063S3WM — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-3
Network type (AC/DC)AC
Network frequency50/60 Hz
C063S3WM — Protection
ParameterValue
Suitability for isolationYes conforming to IEC 60947-3
Electrical durability (cycles)2000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-3
C063S3WM — Mechanical
ParameterValue
Mounting modeWithdrawable
Control typeManually operated
Contact position indicatorYes
Width327 mm
Height210 mm
Depth147 mm
C063S3WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-3
C063S3WM — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The C063S3WM is a basic frame switch disconnector from the Schneider Electric ComPacT NS new generation line. It's a 3-pole, manually operated unit rated 630 A in AC-23A duty across the full voltage range (220 V to 690 V AC), making it a straight choice for motor switching and mixed-load disconnection in distribution panels. The withdrawable chassis means you can rack it out for safe maintenance without disturbing the power wiring — a real time-saver when you're swapping a unit on a live bus.

Rated operational current holds at 630 A across all AC-23A voltages (220/240 V through 660/690 V), so you don't have to derate for higher supply voltages — the full 630 A is available at 690 V. The conventional free-air thermal current (Ith) is also 630 A at 60 °C, which matches the AC-23A number; no thermal bottleneck. Short-time withstand current (Icw) is 25 kA for 0.5 s, giving you headroom for selective coordination with upstream breakers. The 8 kV impulse withstand voltage (Uimp) confirms it's rated for installation in standard 400 V-class distribution with typical surge exposure. The unit carries an IP40 enclosure rating and IK07 impact protection, so it's suited for indoor panel mounting where occasional tool contact or light mechanical shock is expected — not for washdown environments.

Integration notes

Dimensions: 327 mm wide, 210 mm high, 147 mm deep. Withdrawable mounting means the chassis slides into a fixed cradle; plan for the extra depth needed for racking clearance behind the door.

Frequently asked questions

Where can I buy C063S3WM and how is it quoted?

The C063S3WM is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the rated operational current of C063S3WM?

The rated operational current (Ie) is 630 A in AC-23A duty across the full voltage range from 220/240 V to 660/690 V AC at 50/60 Hz.

What standards does C063S3WM comply with?

The C063S3WM complies with IEC 60947-3 for switch-disconnectors, including isolation suitability per that standard.

MPN