The C080H32AFM is a Schneider Electric ComPacT NS new generation 3-pole moulded-case circuit breaker rated 800 A at 50 °C, fitted with a MicroLogic 2.0 A electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection per EN/IEC 60947-2.
Fixed-mount backplate installation with front upside and downside connections. Panel cut-out pitch is 70 mm between phases. The 210 mm width and 327 mm height fit standard distribution panel layouts; depth is 147 mm. IP40 enclosure protection (finger-safe) and IK07 impact resistance suit indoor switchboard environments.
The electronic trip unit includes a thermal memory of 20 minutes, which prevents immediate reclosure after a trip — important for motor or transformer circuits that need cool-down before restart. The LCD display and ammeter measurement give local readout of load current without external metering. Four red LEDs signal fault type; one yellow LED indicates overload condition. Power losses are 15 W at rated current, so ventilation requirements are modest.