Schneider Electric C080H35EFM — Miniature Circuit Breakers (MCB)

Schneider C080H35EFM ComPacT NS 800A 3P MCCB, 70kA 415V

MPNC080H35EFM
Active

Schneider Electric, ComPacT NS new generation, C080H35EFM, 800 A, 3P, MicroLogic 5.0 E electronic trip unit, 70 kA Icu at 415 V AC.

$2,955.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080H35EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C080H35EFM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C080H35EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C080H35EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C080H35EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C080H35EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C080H35EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The Schneider Electric C080H35EFM is a ComPacT NS new generation moulded-case circuit breaker (MCCB) rated 800 A at 50 °C, three-pole, with a MicroLogic 5.0 E electronic trip unit. The 5.0 E provides LSI protection — long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I) — plus integrated energy metering. The 70 kA Icu at 415 V AC (65 kA at 440 V, 50 kA at 525 V) means it interrupts fault currents up to that level without failing, sized for distribution panels where high fault current is expected. The electronic trip unit includes a 20-minute thermal memory, so it remembers prior heating after a trip and re-closes only when the conductor has cooled — critical for motor or feeder circuits where nuisance re-closure risks damage.

Deployment and mounting

Fixed-mount on a backplate, front-connected top and bottom. The 210 mm width and 327 mm height fit standard ComPacT NS switchboard cutouts; the 147 mm depth leaves clearance for rear cable entry. Connection pitch is 70 mm. IP40 enclosure protection (IK07 impact resistance) suits indoor panel installation — not washdown, but fine for dry electrical rooms and MCCs.

Durability and mechanical life

Mechanical durability is 10,000 cycles. Electrical durability depends on load: 2,000 cycles at 690 V at full rated current (In), 4,000 cycles at 690 V at In/2, 5,000 cycles at 440 V at In, and 6,000 cycles at 440 V at In/2. For a distribution breaker seeing infrequent switching, this is ample; for a frequent motor-switching role, the lower electrical endurance at full voltage is the limiting factor.

The utilisation category is B (selective — allows short-time delay for coordination with downstream breakers). Power losses are 15 W at rated current.

Frequently asked questions

How do I get pricing and availability for C080H35EFM?

C080H35EFM is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of C080H35EFM at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. At 440 V it is 65 kA, at 525 V it is 50 kA, and at 690 V it is 42 kA.

What protection functions does the MicroLogic 5.0 E trip unit provide?

LSI protection: long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I). It also includes integrated energy metering and a 20-minute thermal memory.

What is the mounting and connection arrangement for C080H35EFM?

Fixed-mount on a backplate. Both upside and downside connections are front-facing. Connection pitch is 70 mm. Dimensions are 210 mm wide, 327 mm high, 147 mm deep.