Skip to main content
Schneider Electric C080H360FM — Residual Current Breakers (RCCB/RCBO)

Schneider C080H360FM ComPacT NS 800A, 85 kA Icu 240V AC

MPNC080H360FM
Active

Schneider Electric ComPacT NS new generation, C080H360FM, 3P 800 A circuit breaker with MicroLogic 6.0 electronic trip unit, 85 kA Icu at 240 V AC, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080H360FM — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C080H360FM — Electrical Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Number of poles3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Overvoltage categoryIII
Electrical durability2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (operating cycles)10000 cycles
C080H360FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product / component typeCircuit breaker
Product range / familyComPacT
C080H360FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C080H360FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C080H360FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

What this 800 A breaker brings to a distribution panel

The Schneider C080H360FM is a ComPacT NS new generation 3-pole circuit breaker rated 800 A at 50 °C, carrying a MicroLogic 6.0 electronic trip unit. The H breaking capacity code means 85 kA Icu at 220/240 V AC and 70 kA at 380/415 V AC — enough to handle high-fault utility feeds without cascading upstream. The trip unit covers L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground fault) protection, all configurable via the front interface. It is manually operated, fixed-mounted to a backplate, and suited for isolation per EN/IEC 60947-2.

The 85 kA at 240 V AC matters for North American 208/240 V services — it clears a bolted fault at the main before the let-through energy damages branch devices. The 65 kA at 440 V and 50 kA at 500/525 V cover the higher-voltage distribution common in mining or marine installations. Category B utilization means it is listed for selectivity with other breakers in the same series.

Fixed mount to a backplate. Width 210 mm, height 327 mm, depth 147 mm — the depth is the dimension that determines gland-plate clearance in a shallow enclosure. Connection pitch is 70 mm, front-connected both upside and downside. IP40 enclosure rating, IK07 impact resistance. Power dissipation 15 W at rated current — account for that in the panel thermal budget.

Durability and thermal memory

Mechanical endurance is 10 000 cycles. Electrical endurance at full rated current: 2000 cycles at 690 V In, 4000 cycles at 690 V In/2, 5000 cycles at 440 V In, 6000 cycles at 440 V In/2. The MicroLogic 6.0 includes a 20-minute thermal memory — after a trip, it remembers the thermal state of the conductor for that window, preventing nuisance reclose on a still-hot circuit.

Frequently asked questions

How do I get current pricing and availability for C080H360FM?

Submit an RFQ against this order code. Pricing and stock are confirmed at quote time through independent distribution channels.

What is C080H360FM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the MicroLogic 6.0 trip unit provide?

It covers L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection.

MPN
C080H360FM