Skip to main content
Schneider Electric C100L3WM — Miniature Circuit Breakers (MCB)

Schneider Electric C100L3WM ComPacT NS1000L, 150kA at 415VAC

MPNC100L3WM
Active

Schneider Electric ComPacT NS630b...1600 new generation, C100L3WM, basic frame, 1000 A at 50 °C, 150 kA Icu at 415 V AC, 3P, withdrawable, manually operated, without control unit.

$3,970.62 – $6,502.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100L3WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C100L3WM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C100L3WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C100L3WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C100L3WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C100L3WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric C100L3WM is a basic frame from the ComPacT NS630b...1600 new generation range. It is a 3-pole, manually operated, withdrawable circuit breaker frame rated 1000 A at 50 °C, with a breaking capacity of 150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The frame ships without a control unit or protection module; the buyer selects a separate trip unit (Micrologic or similar) to set the protection curve.

At 440 V the Icu drops to 130 kA; at 500/525 V it is 100 kA. The short-time withstand (Icw) is 19.2 kA for 1 second, which supports selective coordination with downstream breakers — the frame holds closed through a downstream fault long enough for the branch breaker to clear it.

Physical integration and mounting

The frame is withdrawable (drawout), meaning the moving portion disconnects from the fixed base for safe maintenance or swap without unbolting cables. Mounting is on a backplate with a 70 mm connection pitch. Dimensions: 260 mm height, 236 mm width, 147 mm depth. The IP40 front face and IK07 impact rating suit indoor panel installation where tools and hands approach the front.

Frequently asked questions

What is the breaking capacity of C100L3WM at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The Ics (service breaking capacity) is the same 150 kA at that voltage, so the frame can be reclosed after clearing a fault at that level.

What is the rated current of C100L3WM?

1000 A at 50 °C ambient. The frame is rated for distribution applications per IEC 60947-2.

Does C100L3WM include a trip unit or protection module?

No. The C100L3WM is a basic frame only — it ships without a control unit or integral protection. The buyer selects a separate Micrologic or equivalent trip unit to set the protection curve and settings.

How do I get current pricing and availability for C100L3WM?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

MPN