Skip to main content
Schneider Electric C100L4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C100L4WM ComPacT NS1000L Frame, 150 kA at

MPNC100L4WM
Active

Schneider Electric ComPacT NS1000L basic frame, C100L4WM, 1000 A at 50 °C, 150 kA Icu at 415 VAC, 4P withdrawable, manually operated, without control unit.

$8,381.88Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100L4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C100L4WM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C100L4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C100L4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C100L4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C100L4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The C100L4WM is a basic frame (no trip unit) in the Schneider ComPacT NS630b...1600 new generation range, rated 1000 A at 50 °C and built for distribution duty per IEC 60947-2. It is a 4-pole, withdrawable, manually operated chassis — you fit a separate electronic or micrologic control unit to set the protection curves.

The 1000 A rating is at 50 °C ambient — if your panel runs hotter, you derate per the manufacturer's curve. Withdrawable mounting means the chassis slides out of its cradle for inspection or swap without disturbing the main bus connections — common in high-availability switchgear where downtime is measured in minutes.

Current-production item — no end-of-life notice on record. The ComPacT NS new generation line is Schneider's active platform for 630–1600 A frames.

Mounts on a backplate (not DIN rail) — the 306 mm width, 260 mm height, and 147 mm depth require a dedicated cutout in the switchboard. Connection pitch is 70 mm between pole centers. The frame is IP40 (finger-safe) and IK07 (impact-resistant), so it can sit behind a locked door without additional shrouding.

Frequently asked questions

What is the breaking capacity of C100L4WM at 415 V?

150 kA Icu and 150 kA Ics at 380/415 V AC 50/60 Hz per IEC 60947-2 — the frame can interrupt and be reused after a fault at that level.

What compliance documentation does Schneider provide for C100L4WM?

The frame is designed and tested to IEC 60947-2, with IP40 per IEC 60529, IK07 per EN 50102, pollution degree 3, overvoltage category III, and suitability for isolation per EN/IEC 60947-2. RoHS/REACH declarations are standard for the ComPacT range.

MPN