Skip to main content
Schneider Electric C100L32AFM — Miniature Circuit Breakers (MCB)

C100L32AFM ComPacT NS 3P 1000A MicroLogic 2.0 A, 150 kA 415V

MPNC100L32AFM
Obsolete

Schneider Electric ComPacT NS new generation, C100L32AFM, 3P fixed circuit breaker, 1000 A at 50 °C, MicroLogic 2.0 A electronic trip unit, 150 kA Icu at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100L32AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C100L32AFM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C100L32AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C100L32AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100L32AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C100L32AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C100L32AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C100L32AFM is a fixed-mount, manually operated ComPacT NS new generation circuit breaker from Schneider Electric, part of the NS630b...1600 range. It carries a MicroLogic 2.0 A electronic trip unit rated 1000 A at 50 °C, with L (long-time overload) and I (instantaneous short-circuit) protection curves. The 3P fixed form factor bolts to a backplate with a 70 mm connection pitch and front-facing terminals, so it fits standard switchboard busbar layouts without adapters. The electronic trip unit includes a 20-minute thermal memory, which prevents nuisance reclosing after a sustained overload by retaining the thermal model of the conductors. The LCD display and ammeter measurement give local readout of load current without a separate panel meter. Four red LEDs signal fault type; one yellow LED indicates overload pre-alarm.

Mounts fixed to a backplate inside a distribution switchboard or panel enclosure. The 327 mm height, 210 mm width, and 147 mm depth fit standard cubicle compartments; the 70 mm connection pitch matches common busbar drilling patterns. Front-side upside and downside connections simplify busbar routing and cable termination.

Electrical durability and operating limits

Rated for 10,000 mechanical cycles and 2,000 electrical cycles at full rated current (1000 A at 690 V), with higher cycle counts at reduced loads — 3,000 cycles at In/2 at 690 V, 3,000 cycles at In at 440 V, and 4,000 cycles at In/2 at 440 V. Ambient relative humidity range 0–95 %.

Frequently asked questions

Where can I buy C100L32AFM?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is C100L32AFM's breaking capacity at 415 V?

150 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which means it safely interrupts fault currents up to that level without upstream cascading.

What protection curves does the MicroLogic 2.0 A trip unit provide?

L (long-time overload) and I (instantaneous short-circuit) protection, with a 20-minute thermal memory to prevent nuisance reclosing after overloads.

What compliance standards does C100L32AFM meet?

Designed and tested to EN/IEC 60947-2 for low-voltage switchgear and controlgear. Pollution degree 3 and overvoltage category III per IEC 60947.

MPN