The Schneider Electric C100L42AFM is a ComPacT NS new generation molded case circuit breaker (MCCB) from the NS630b...1600 range, rated 1000 A at 50 °C with a MicroLogic 2.0 A electronic trip unit providing L (long-time overload) and I (instantaneous short-circuit) protection.
Fixed-mount backplate installation with front upside and downside connections; 70 mm connection pitch. At 327 x 280 x 147 mm (H x W x D) and IP40, it fits inside a standard distribution enclosure with gland-plate clearance for the 4-pole, neutral-left configuration.
Listed as current-production lifecycle stage.
The LCD display and ammeter measurement type provide local metering. Four red LEDs for fault indication and one yellow LED for overload. Thermal memory of 20 minutes. Electrical durability: 2000 cycles at 690 V In, 3000 at 690 V In/2, 3000 at 440 V In, 4000 at 440 V In/2. Mechanical durability: 10000 cycles.