Schneider Electric C10H42D040 — Miniature Circuit Breakers (MCB)

Schneider C10H42D040 ComPacT NSX100H, 40 A, 100 kA Icu

MPNC10H42D040
Active

Schneider Electric ComPacT NSX, NSX100H, circuit breaker, 40 A, 100 kA Icu at 240 V AC, MicroLogic 2.2 electronic trip unit, 4P, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10H42D040 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H42D040 — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H42D040 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H42D040 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10H42D040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H42D040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H42D040 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range18...40 A
Trip unit protection functionsLSoI

Product details

The Schneider C10H42D040 is a ComPacT NSX100H molded-case circuit breaker with a 40 A MicroLogic 2.2 electronic trip unit, four poles, and a 100 kA interrupting capacity at 240 V AC. At 415 V AC the breaking capacity is 70 kA Icu, and at 480 V AC it holds 65 kA Icu. The MicroLogic 2.2 trip unit provides LSI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). No earth-leakage protection is built in, so if ground-fault detection is required, add a Vigi module or external relay. Above 40 °C, derate per the IEC 60947-2 thermal curve. The 4P configuration places the neutral on the left, and the device is category A (no intentional short-time delay for selectivity with downstream breakers — selectivity relies on the MicroLogic's adjustable curves).

Deployment context: panel integration and environment

Mounts on a backplate in any orientation — horizontal, vertical, or flat on the back. The 140 mm width, 161 mm height, and 86 mm depth fit standard distribution panel cutouts; the 35 mm connection pitch matches busbar systems and common terminal blocks. IP40 enclosure protection means it is suitable for indoor panels where no water spray is present; the IK07 impact rating handles accidental tool strikes during commissioning. Connections are front-access both top and bottom, so the breaker can be wired without reaching behind the panel. Five accessory slots accept auxiliary contacts, shunt trips, undervoltage releases, or communication modules — leaving room for future expansion without swapping the breaker frame.

The NSX100H frame (100 A frame, H breaking capacity) is the same mechanical platform used across the 40 A to 100 A trip unit range. If a higher or lower amp rating is needed later, the MicroLogic 2.2 trip unit can be swapped without replacing the breaker base — but the order code C10H42D040 is fixed at 40 A. No direct pin-compatible second source exists; the ComPacT NSX is a proprietary Schneider design.