Skip to main content
Schneider Electric C10H44V040 — Residual Current Breakers (RCCB/RCBO)

C10H44V040 ComPacT NSX100H 40A 4P MCCB, 100kA Icu at 240V

MPNC10H44V040
Obsolete

Schneider Electric ComPacT NSX series, NSX100H, 40 A, 4-pole MCCB with MicroLogic 4.2 electronic trip unit, 100 kA Icu at 240 V AC, integrated earth-leakage protection.

$1,172.06 – $2,246.40Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H44V040 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10H44V040 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (operating cycles)50000 cycles
C10H44V040 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX100H
C10H44V040 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10H44V040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10H44V040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C10H44V040 is a Schneider Electric ComPacT NSX100H 4-pole MCCB rated 40 A at 40 °C, built around the MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection. At 415 V AC the breaking capacity is 70 kA Icu; at 440 V AC it's 65 kA Icu, so the part holds its interrupting rating well into the 400 V class, not just at low voltage.

Trip unit and protection logic

The MicroLogic 4.2 is an electronic trip unit offering L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection — all in one package. Earth-leakage is integrated, not a bolt-on accessory, which simplifies panel wiring and reduces the component count per feeder.

Dimensions: 161 mm H × 140 mm W × 86 mm D. IP40 front face, IK07 impact rating.

Frequently asked questions

What is C10H44V040's listed range (ComPacT) on this component line?

The range is ComPacT, specifically the ComPacT NSX series.

What compliance documentation does this brand provide for C10H44V040 (RoHS, REACH, UL, IEC)?

The MCCB is certified to EN/IEC 60947-2 and UL 60947-4-1. The IP40 and IK07 ratings are per IEC 60529 and IEC 62262 respectively. Pollution degree 3 per IEC 60664-1.

MPN
C10H44V040