Skip to main content
Schneider Electric C10H32D040 — Miniature Circuit Breakers (MCB)

C10H32D040 ComPacT NSX100H 40A 3P 100kA Circuit Breaker

MPNC10H32D040
Active

Schneider Electric ComPacT NSX, NSX100H, C10H32D040, 3P 40A 100kA Icu at 240V AC circuit breaker with MicroLogic 2.2 electronic trip unit.

$354.45 – $893.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10H32D040 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H32D040 — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H32D040 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H32D040 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10H32D040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H32D040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H32D040 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range18...40 A
Trip unit protection functionsLSoI

Product details

The C10H32D040 is a Schneider Electric ComPacT NSX100H 3-pole circuit breaker rated 40 A at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. It carries a 100 kA Icu breaking capacity at 220/240 V AC (50/60 Hz) per IEC 60947-2, which means it can safely interrupt fault currents up to that level without upstream devices needing to clear the fault — a key selectivity headroom for distribution panels feeding downstream subfeeds. The electronic trip provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, settable to coordinate with downstream breakers.

Breaking capacity across voltage levels

The H breaking capacity code delivers 70 kA Icu at 380/415 V AC, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V AC. For UL 60947-4-1 applications, it offers 85 kA at 240 V AC, 65 kA at 480 V, and 10 kA at 600 V. This voltage-dependent curve is typical of molded-case breakers: the interrupting rating drops as voltage rises.

Mounts on a backplate in either horizontal or vertical orientation, flat on the back. Front connections on both upside and downside simplify busbar and cable routing in a panel. The 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. IP40 front-face protection and IK07 impact resistance suit enclosed distribution boards.

Rated for 50,000 mechanical cycles and 50,000 electrical cycles at 440 V at half rated current (In/2), 30,000 cycles at 440 V at In, 20,000 cycles at 690 V at In/2, and 10,000 cycles at 690 V at In. The breaker is certified suitable for isolation per EN/IEC 60947-2, meaning it can be used as a visible-break disconnect when locked in the off position.

Frequently asked questions

What is C10H32D040's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What trip unit does C10H32D040 use?

A MicroLogic 2.2 electronic trip unit providing L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection.

Where can I buy C10H32D040?

The C10H32D040 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does this brand provide for C10H32D040?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1 standards. It carries IP40 and IK07 protection ratings, and is rated for pollution degree 3 per IEC 60664-1.

MPN
C10H32D040