The 32 A rating at 50 °C means it carries that current continuously in a 50 °C ambient without nuisance tripping — derate above that per IEC 60947-2. The 50 kA Icu at 415 V AC tells you this breaker safely interrupts a 50 kA fault at that voltage; the full breaking curve runs from 90 kA at 240 V down to 10 kA at 690 V, so it fits distribution panels where the available fault current at the line side is known. The 3-pole (3P) form factor with front-connect terminals bolts onto a backplate and accepts a 35 mm connection pitch.
Schneider still manufactures this as an active catalog item. No end-of-life notice or last-time-buy date is published.
Deployment context
Mounts on a backplate inside an electrical enclosure. The toggle control gives local manual on/off; suitability for isolation means it can serve as a visible-disconnect point when locked off.
The IK07 rating means it withstands a 2 J impact (e.g., a dropped tool). Electrical durability is 50,000 cycles at 440 V In/2 and 30,000 cycles at full rated current; mechanical durability is 50,000 cycles. Power dissipation is 4.03 W per pole, useful for panel thermal calculations.