The TM-D trip gives you L (thermal overload) and I (magnetic short-circuit) protection in one unit — no ground-fault module here, so if earth-leakage is needed, you add a Vigi add-on block externally. IP40 enclosure protection, IK07 impact resistance.
The N breaking-capacity code means 50 kA Icu at 380/415 V and 440 V AC, 90 kA at 220/240 V, and it still holds 36 kA at 500 V and 10 kA at 690 V. Under UL 60947-4-1 it's rated 85 kA at 240 V, 50 kA at 480 V, 10 kA at 600 V. That's a wide voltage range — useful if the same breaker model is specified across different line voltages in a plant.
For volume or scheduled releases, confirm pricing and lead time at quote.
Integration notes
Four-pole version (4P) with neutral on the left. Neutral protection set to 1 x Ir (full phase current). Electrical durability: 50,000 cycles at 440 V at half rated current, 30,000 at full In. Mechanical durability 50,000 cycles.