Skip to main content
Schneider Electric C10N4TM025 — Miniature Circuit Breakers (MCB)

Schneider C10N4TM025 ComPacT NSX 25A 4P MCCB, 50 kA at 415V

MPNC10N4TM025
Active

Schneider Electric ComPacT NSX, NSX100N, 4P, 25 A at 40 °C, TM-D trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2, UL 60947-4-1.

$232.67 – $648.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N4TM025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N4TM025 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N4TM025 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N4TM025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N4TM025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N4TM025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N4TM025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 25 A figure is the trip-unit rating at 40 °C ambient; if your panel runs hotter, you derate per the IEC 60947-2 thermal curve. The TM-D gives you fixed thermal overload (L) and fixed magnetic short-circuit (I) protection — no adjustable dials, so what you see on the nameplate is what you get for coordination studies. At 480 V AC it delivers 50 kA Icu under UL 60947-4-1.

This breaker mounts to a backplate — no DIN rail required. The enclosure itself provides the environmental seal. IK07 impact resistance handles accidental tool drops during panel work.

Frequently asked questions

What compliance documentation comes with the C10N4TM025?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries suitability for isolation per EN/IEC 60947-2, pollution degree 3 per IEC 60664-1, and overvoltage category III. Schneider provides the declaration of conformity and test certificates with the shipment.

MPN
C10N4TM025