The 25 A figure is the trip-unit rating at 40 °C ambient; if your panel runs hotter, you derate per the IEC 60947-2 thermal curve. The TM-D gives you fixed thermal overload (L) and fixed magnetic short-circuit (I) protection — no adjustable dials, so what you see on the nameplate is what you get for coordination studies. At 480 V AC it delivers 50 kA Icu under UL 60947-4-1.
This breaker mounts to a backplate — no DIN rail required. The enclosure itself provides the environmental seal. IK07 impact resistance handles accidental tool drops during panel work.