Skip to main content
Schneider Electric C10N4TM016C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N4TM016C ComPacT NSX MCCB, 16 A, 50 kA

MPNC10N4TM016C
Active

Schneider Electric ComPacT NSX, MCCB, 4P, 16 A, 50 kA Icu at 415 V AC, TM-D trip unit, IP40, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N4TM016C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N4TM016C — Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N4TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N4TM016C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N4TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N4TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N4TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

MCCB for distribution panels — 16 A, 50 kA at 415 V

The C10N4TM016C is a 4-pole ComPacT NSX100N MCCB from Schneider Electric's ComPacT range, fitted with a TM-D thermal-magnetic trip unit rated 16 A at 50 °C. It breaks 50 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2, which covers the fault-current capability needed for most commercial and light-industrial distribution boards. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection in a single block — no separate trip unit to source.

At 220/240 V that figure rises to 90 kA Icu; at 690 V it drops to 10 kA Icu.

Mounts flat on a backplate — no DIN-rail adapter. The 140 mm width, 161 mm height, and 86 mm depth fit standard distribution panel cutouts for 4-pole MCCBs. IP40 enclosure protection means it's suited for indoor panels; IK07 impact resistance handles incidental tool contact during commissioning.

Rated for 50,000 mechanical operations and 30,000 electrical cycles at rated current (440 V, In). At half-rated current that doubles to 50,000 electrical cycles. For a distribution breaker seeing infrequent switching (a few operations per month), this translates to decades of service life. The TM-D trip unit is field-replaceable if the thermal or magnetic calibration drifts.

Frequently asked questions

What is the breaking capacity of C10N4TM016C at 415 V?

50 kA Icu at 380/415 V AC per IEC 60947-2. That is the N breaking capacity code — sufficient for most 400 V distribution boards up to about 1.5 MVA transformer rating.

Where can I buy C10N4TM016C?

Sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What standards does C10N4TM016C comply with?

Designed and tested to EN/IEC 60947-2 for low-voltage switchgear and controlgear. Suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

What is the closest alternative to C10N4TM016C in the same family?

Within the ComPacT NSX100N frame, the same 4-pole MCCB with a higher trip rating (e.g., 25 A or 32 A) uses the same physical footprint and breaking capacity. If you need a different trip curve, the TM-D is thermal-magnetic; the Micrologic electronic trip units (2.0, 5.0, 6.0) fit the same NSX100N frame but require a different order code.

MPN