C10N4TM025C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N4TM025C — Ratings
ParameterValue
Rated current (In)25 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N4TM025C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N4TM025C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N4TM025C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N4TM025C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N4TM025C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10N4TM025C is a Schneider Electric ComPacT NSX100N molded-case circuit breaker, 4-pole, fitted with a TM-D thermal-magnetic trip unit rated 25 A at 50 °C. It belongs to the NSX100 frame (device short name NSX100N) and carries an N breaking capacity code — 50 kA Icu at 415 V AC per IEC 60947-2. That puts it squarely in the distribution-grade MCCB class for commercial and light industrial switchboards where you need high interrupting capacity in a compact footprint (161 mm H × 140 mm W × 86 mm D).

The 25 A thermal-magnetic trip (TM-D) handles overload protection via a thermal bimetal (L protection) and short-circuit protection via a magnetic solenoid (I protection). At 50 °C ambient the breaker is rated full 25 A without derating — important if your panel runs warm. The breaking capacity curve is the real selector: 90 kA Icu at 240 V AC, 50 kA at 415 V, and it still holds 35 kA at 525 V and 10 kA at 690 V. For a 400 V distribution board, the 50 kA Icu gives solid headroom against most utility fault levels. The 4-pole version (neutral left, 1 x Ir setting) suits three-phase plus neutral systems where you want the neutral switched and protected.

Integration and mounting notes

Front connections both upside and downside. IK07 impact rating handles incidental tool drops.

Overvoltage category III, utilization category A. Electrical endurance: 50,000 cycles at 440 V at half rated current, 30,000 at full rated current. Mechanical durability: 50,000 cycles. The breaker carries no integral earth-leakage protection (add a Vigi module externally if needed).

Frequently asked questions

What is the breaking capacity of C10N4TM025C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 220/240 V it rises to 90 kA Icu; at 690 V it holds 10 kA Icu.

Where can I buy C10N4TM025C?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What trip unit does C10N4TM025C use?

A TM-D thermal-magnetic trip unit rated 25 A at 50 °C. It provides L protection (thermal overload) and I protection (magnetic short-circuit).

Does this MCCB include earth-leakage protection?

No, the base breaker ships without earth-leakage protection. A Vigi external earth-leakage module can be added if required.