The C10N6TM063C is a Schneider Electric ComPacT NSX100N frame circuit breaker, 4-pole, rated 63 A at 50 °C with a thermal-magnetic TM-D trip unit. It provides L (overload) and I (short-circuit) protection per EN/IEC 60947-2, with a breaking capacity of 50 kA Icu at 380/415 V AC 50/60 Hz. The TM-D trip unit is fixed thermal and magnetic; no interchangeable rating plugs, so the 63 A is what you get.
Schneider Electric C10N6TM063C ComPacT NSX 63A, 50kA 415V AC
Schneider Electric ComPacT NSX, circuit breaker, 63 A, 4P, thermal-magnetic TM-D trip unit, 50 kA Icu at 415 V AC, IP40, backplate mount.
Specifications
| Parameter | Value |
|---|---|
| Product name | ComPacT NSX |
| Product range | ComPacT |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 63 A at 50 °C |
| Poles configuration | 4P |
| Breaking capacity | 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated service breaking capacity (Ics) | 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Electrical durability (cycles) | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
| Mechanical durability (cycles) | 50000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
What is the breaking capacity of C10N6TM063C at 415 V?
50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the N breaking capacity code — sufficient for most industrial distribution boards downstream of a 1 MVA transformer.
What protection does the TM-D trip unit provide?
L (thermal) for overload protection and I (magnetic) for short-circuit protection. The thermal element is fixed at 63 A at 50 °C; the magnetic pickup is fixed as well — no interchangeable rating plugs or adjustment dials.
Does C10N6TM063C include earth-leakage protection?
No, it ships without earth-leakage protection. If ground-fault protection is needed, an external Vigi module or separate RCD must be added upstream.
Where can I buy C10N6TM063C?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.