Skip to main content
Schneider Electric C10N6TM063C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N6TM063C ComPacT NSX 63A, 50kA 415V AC

MPNC10N6TM063C
Active

Schneider Electric ComPacT NSX, circuit breaker, 63 A, 4P, thermal-magnetic TM-D trip unit, 50 kA Icu at 415 V AC, IP40, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N6TM063C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N6TM063C — Ratings
ParameterValue
Rated current (In)63 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N6TM063C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N6TM063C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N6TM063C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N6TM063C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N6TM063C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10N6TM063C is a Schneider Electric ComPacT NSX100N frame circuit breaker, 4-pole, rated 63 A at 50 °C with a thermal-magnetic TM-D trip unit. It provides L (overload) and I (short-circuit) protection per EN/IEC 60947-2, with a breaking capacity of 50 kA Icu at 380/415 V AC 50/60 Hz. The TM-D trip unit is fixed thermal and magnetic; no interchangeable rating plugs, so the 63 A is what you get.

Frequently asked questions

What is the breaking capacity of C10N6TM063C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the N breaking capacity code — sufficient for most industrial distribution boards downstream of a 1 MVA transformer.

What protection does the TM-D trip unit provide?

L (thermal) for overload protection and I (magnetic) for short-circuit protection. The thermal element is fixed at 63 A at 50 °C; the magnetic pickup is fixed as well — no interchangeable rating plugs or adjustment dials.

Does C10N6TM063C include earth-leakage protection?

No, it ships without earth-leakage protection. If ground-fault protection is needed, an external Vigi module or separate RCD must be added upstream.

Where can I buy C10N6TM063C?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
C10N6TM063C