What the 200 kA breaking capacity means for your panel
The C10R32D040 is a Schneider Electric ComPacT NSX100R molded-case circuit breaker, 3-pole, rated 40 A at 40 °C with a MicroLogic 2.2 electronic trip unit. For a distribution panel fed from a large transformer or a high-capacity bus, that rating means you do not need an upstream current-limiting fuse; the breaker itself handles the full available fault current at the board.
Integration and mounting — backplate, not DIN rail
Mounts on a backplate (not a DIN rail) in horizontal or vertical orientation, flat on the back. Front connections top and bottom simplify bus-bar or cable landing in a panel layout. The 105 mm width and 161 mm height fit the standard ComPacT NSX footprint; depth is 86 mm, which matters for enclosure depth clearance when the door-mounted rotary handle is used. IP40 front face (IK07 impact rating) means it is protected against tools and small solids but not washdown — fine for a dry indoor panel, not for a food-processing floor.