Skip to main content
Schneider Electric C10R32M025 — Miniature Circuit Breakers (MCB)

Schneider Electric C10R32M025 ComPacT NSX 25A 3P MCCB, 200kA

MPNC10R32M025
Active

Schneider Electric, ComPacT NSX, MCCB, C10R32M025, 25 A, 3P, 200 kA Icu at 415 V, MicroLogic 2.2 M electronic trip unit, motor protection.

$16.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R32M025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C10R32M025 — Ratings
ParameterValue
Rated current (In)25 A at 65 °C
Poles configuration3P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10R32M025 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10R32M025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C10R32M025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10R32M025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10R32M025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range12...25 A
Trip unit protection functionsLSoI

Product details

What this ComPacT NSX brings to the panel

The C10R32M025 is a 3-pole ComPacT NSX100R frame MCCB rated 25 A, built around the MicroLogic 2.2 M electronic trip unit. It's specified for motor protection — the trip unit offers L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, with motor tripping classes 5, 10, and 20 selectable. That means it's tuned for the inrush and thermal characteristics of a motor load, not just a distribution feeder. At 690 V it still breaks 45 kA. The part is rated per EN/IEC 60947-2, utilization category A (no intentional short-time delay for selectivity).

Motor protection detail — the trip unit matters

The MicroLogic 2.2 M is an electronic trip unit, not a thermal-magnetic. Motor tripping classes 5, 10, and 20 are selectable; class 20 is the default for standard induction motors, class 10 for faster protection on submersible or high-torque loads.

Fit and mounting — panel-side notes

Mounts on a backplate — no DIN rail here. Connection pitch is 35 mm, with both upside and downside front connections. Pollution degree 3 (conductive pollution, typical for industrial enclosures), overvoltage category III. IP40 front face, IK07 impact resistance — it's sealed against tools and fingers but not washdown. Horizontal or vertical mounting, flat on the back. Five accessory slots on the breaker. The local signalling includes a green flashing LED for ready-to-operate and a red LED at 95 % Ith for temperature over set point. No earth-leakage protection integrated — that's handled by separate Vigi add-on modules if needed.

Frequently asked questions

What is C10R32M025's listed range (ComPacT) on this component line?

The range is ComPacT, and the product name is ComPacT NSX — Schneider Electric's main molded-case circuit breaker family for industrial and commercial distribution.

What is C10R32M025's listed depth (d) (86 mm) on this component line?

The depth is 86 mm. Width is 105 mm, height is 161 mm. Connection pitch is 35 mm.

MPN